Michell Easidew PRO I.S. Intrinsically Safe Dew Point Transmitter: Selection and InstallationHydrates in gas lines, corrosion inside pipework, failed instruments downstream — the source is usually moisture. When the sample point sits in a classified area, a 4–20 mA intrinsically safe dew point transmitter decides whether the monitoring system survives on site. The Michell Easidew PRO I.S. is one of the most frequently specified dew point transmitters for that duty. This article covers where it fits, and the practical points for natural gas dew point measurement and compressed air dew point monitoring.
One dew point transmitter, two media
The Easidew PRO I.S. measures moisture in gases and in hydrocarbon liquids. The dew point range runs from −110 to +20 °Cdp, and the 4–20 mA output can be re-scaled to ppmV for gas applications. Accuracy is ±1 °Cdp between +20 and −60 °C; below −60 °Cdp it is ±2 °Cdp, which suits the very dry end where users track trend rather than a single laboratory figure.
A two-wire 4–20 mA loop means this dew point transmitter drops into an existing DCS, PLC or display without a special input card.
Intrinsically safe is not explosion proof
This is the mistake buyers make most often. The PRO I.S. is intrinsically safe: it must run through a galvanic isolator or Zener barrier, and the whole loop must be certified as an IS circuit. It is not a flameproof housing you can wire straight into a standard panel.
Approvals cover ATEX (Baseefa06ATEX0330X), IECEx (IECEx BAS 060090X), UKCA, cQPSus for the US and Canada, TR CU Ex for the Eurasian market, plus NEPSI and Japanese Ex. When a project mixes European, North American and CIS equipment standards, this certification set is the reason to choose Michell over a regional-only brand.
Natural gas dew point measurement and compressed air dew point monitoring
- Natural gas processing, transmission lines and city-gate metering
- Biomethane, CNG and LNG filling stations
- Compressed air dryers, where dew point is the acceptance criterion
- Hydrogen coolant loops and heat-treating furnace atmospheres
- Water content control in hydrocarbon liquids
The 13-point traceable calibration certificate and BS EN 10204 3.1 material certification go straight into a buyer's inspection package — one of the usual reasons shipments get held at customs or at site reception.
Specifying a dew point transmitter: five checks
- Sample conditioning first. Fit a coalescing filter and fix the flow rate; most early failures are contamination, not electronics.
- Pressure compensation. If you read ppmV, the actual line pressure must be programmed into the transmitter, or the value is wrong.
- Barrier matching. Confirm the isolator's gas group and temperature class match the dew point transmitter.
- Process connection and adapters. Order them with the unit; a missing adapter stops commissioning.
- Sensor exchange. Michell runs a service exchange programme — plan the spare instead of buying a second transmitter.
Keep these references to hand when checking compatibility:ATEX Baseefa06ATEX0330X,IECEx BAS 060090X, range −110 to +20 °Cdp.
If you are unsure whether your loop is already IS-rated, send us the barrier model and the area classification drawing, and we will confirm compatibility before shipping.